UPS Control Help
 

This page allows the manual control of the main output and switchable outputs of the UPS.

The status of each output is shown by an icon associated with the label Off (icon red) or On (icon green).

Warning : when a On/off sequence is in progress, the output status is not updated when the sequence is completed.

The column Control contains a list of six different commands :
Safe power down : A shutoff sequence of the outlet is launched immediately. The system powered by the output stops during the shutoff sequence and the output is stopped.
Safe power down & reboot : A sequence containing a shutoff command followed by a restart command is launched immediately. The system powered by the output stops during the shutoff sequence and the output is stopped.
Then the output restarts when the Toggle Duration has expired.
Immediate On : A restart sequence of the outlet is launched immediately. The output is powered and the system powered by the output restart.
Delayed, safe power down : This is the same shutoff sequence as the command 'Safe power down' but it is delayed with the number of seconds programmed into the parameter 'Off Delay'.
Delayed, safe power down & reboot : This is the same sequence as the command 'Safe power down & reboot' but it is delayed with the number of seconds programmed into the parameter 'Off Delay'.
Delayed On : This is the same restart sequence than the command 'Safe power down' but it is delayed with the number of seconds programmed into the parameter 'On Delay'.

The parameters Off Delay, Toggle Duration and On Delay can be kept into saved memory with the Save button.